UIPL TORQMAX™
Silent Diesel Gensets — Single & Three Phase at 50 Hz
From 2.5 kVA to 22.5 kVA. Air-cooled and water-cooled variants with AVR voltage regulation.
Performance Testing & Validation
Every TORQMAX genset is tested in-house against standardised load, voltage regulation, and fuel efficiency parameters before dispatch. Select phase type to view the corresponding curves.
Load vs Output Voltage
230V SPLoad vs Fuel Consumption
230V SPGenset Variants
Air-cooled for compact setups, water-cooled for continuous duty and higher kVA.
Single Phase Gensets — 230V @ 50 Hz
Power factor 1.0. Ideal for domestic backup, farm equipment, and single-phase industrial loads.
Three Phase Gensets — 415V @ 50 Hz
Power factor 0.8. For industrial motors, workshops, and three-phase distribution.
Full Specifications
Note: 1 HP = 0.735 kW. All gensets rated at 1500 RPM.
Generator for Welding Applications
Technical sizing guide for powering transformer-type and inverter-type welding machines from a diesel genset. Design basis: IS 2635, IEC 60974-1, IS 4722.
| Welding Process | Welder Type | OCV (V DC) | Welding Current (A) | Arc Voltage (V) | Duty Cycle | Welder Input (kVA) | Derating × 1.25 | Min. Genset (kVA) | Voltage Reg. Req. |
|---|---|---|---|---|---|---|---|---|---|
| SMAW Stick / MMA | Transformer / Rectifier | 80 | up to 200 A | 22 – 26 V | 60 % | 5.5 – 6.5 | 6.9 – 8.1 | 10 kVA | ± 5 % |
| SMAW Stick / MMA | Transformer / Rectifier | 80 | up to 300 A | 26 – 32 V | 60 % | 9.0 – 10.5 | 11.3 – 13.1 | 15 kVA | ± 5 % |
| SMAW Stick / MMA | Transformer / Rectifier | 80 | up to 400 A | 30 – 36 V | 60 % | 13.5 – 15.5 | 16.9 – 19.4 | 20 kVA | ± 5 % |
| MIG / MAG GMAW | Inverter (IGBT) | 65 | up to 200 A | 18 – 24 V | 35 % | 7.0 – 9.0 | 8.8 – 11.3 | 15 kVA | ± 2.5 % |
| TIG GTAW / DCEN | Inverter (IGBT) | 65 | up to 200 A | 10 – 20 V | 40 % | 5.5 – 7.0 | 6.9 – 8.8 | 10 kVA | ± 2.5 % |
| Plasma Cutting PAC | Inverter (IGBT) | 120 – 360 | up to 200 A | 100 – 180 V | 50 % | 9.0 – 12.0 | 11.3 – 15.0 | 15 kVA | ± 2.5 % |
| SAW Submerged Arc | Rectifier / Thyristor | 80 | up to 600 A | 28 – 40 V | 100 % | 22.0 – 28.0 | 27.5 – 35.0 | 35 kVA | ± 5 % |
Harmonic Distortion (THD)
IGBT inverter welders are non-linear loads generating 3rd, 5th, and 7th order harmonics. Generator must be specified with a short-circuit ratio ≥ 3 and AVR bandwidth sufficient to suppress voltage distortion. THD ≤ 5 % at rated load per IEC 61000-3-2.
Starting / Inrush Current
Transformer-type welders draw 3–4 × rated current at switch-on. Inverter-type draw lower inrush (~1.5×) but may cause AVR hunting. Generator transient voltage dip must remain < 15 % for < 1.5 s to maintain arc stability.
Duty Cycle & Thermal Rating
IS 2635 defines duty cycle at 10-minute base period. At 60 % DC, the welder draws rated current for 6 minutes, rests for 4. Generator thermal capacity must be sized for continuous equivalent load, not peak: Irms = Ipeak × √(DC).
Power Factor & AVR Response
Transformer welders operate at PF 0.55 – 0.70 lagging. Inverter welders correct to ~0.85–0.95. Generator AVR must respond within ≤ 300 ms to load step changes. Brushless self-excited alternators with digital AVR are preferred.
Parallel / Multi-Point Welding
For n simultaneous welding stations, apply a simultaneity factor k = 0.65 – 0.75. Total genset kVA = Σ(welderi kVA) × k × 1.25. Example: 4 × 300 A SMAW welders → 4 × 10 kVA × 0.70 × 1.25 = 35 kVA genset.
VRD — Voltage Reduction Device
Per IS 13203, VRD limits OCV to ≤ 35 V DC between weld cycles. When VRD is active, the welding circuit switches to low voltage instantly on arc break. Generator must support this rapid load switching without voltage hunting or AVR instability.
Altitude & Ambient Derating
Standard IS 4722 genset rating is at 1000 m ASL, 40 °C. Derate output by 1 % per 100 m above 1000 m and 3 % per 5 °C above 40 °C. At 45 °C ambient: effective output = rated kVA × 0.97 — recalculate required rating accordingly.
Voltage Regulation & Arc Stability
Arc voltage droop during welding directly degrades bead geometry. For SMAW, ± 5 % steady-state regulation is acceptable. For MIG/MAG and TIG, ± 2.5 % is mandatory. Upkar AVR-equipped gensets maintain ± 1 % under regulated load.
GenkVA = (Varc × Iweld / 1000) × (1 / PFgen) × 1.25
GenkVA = Σ(Vi × Ii / 1000) × k × (1 / PFgen) × 1.25
Irms = Irated × √(DC / 100)
Industrial Engines
4-cylinder diesel prime movers for high-demand industrial gensets — 40 kVA to 82.5 kVA. Built for continuous duty, export-grade quality.
| KVA Rating | Output (kW) | Engine Power (HP) | Cylinders | cos φ (p.f.) |
|---|---|---|---|---|
| 40 kVA | 32 kW | 56 HP | 4 | 0.8 |
| 50 kVA | 42 kW | 62 HP | 4 | 0.8 |
| 62.5 kVA | 50 kW | 83 HP | 4 | 0.8 |
| 82.5 kVA | 70 kW | 105 HP | 4 | 0.8 |
All engines rated at 1500 RPM. 4-Stroke direct injection diesel. Power factor 0.8.
Standard Build Features
AVR Regulated
Voltage regulation within ±1% using automatic voltage regulator
4-Stroke Diesel
Single/twin cylinder, naturally aspirated diesel engine
Starting System
Manual and electric start options available
Coupling
Flexible lovejoy or rubber coupling for vibration isolation
Heavy-Duty Bearings
Ball bearings rated for extended continuous operation life
1500 RPM
Ideal rated speed for clean 50 Hz power output
Mounting Options
Fixed base frame, trolley base with wheels, skid-mounted, or silent canopy — as required
Key Features
Stable Power Output
AVR-regulated voltage within ±1% — safe for sensitive equipment and electronics.
Fuel Efficient
Direct injection diesel engines optimized for low fuel consumption at rated load.
Dual Cooling
Air-cooled for light duty and portability, water-cooled for continuous heavy loads.
Low Vibration
Flexible coupling and balanced rotating assembly for smooth, quiet operation.
Easy Maintenance
Accessible components, standard spares, and clear service intervals for field repair.
Export Ready
ISO-certified quality, export-grade packing, and worldwide spares support.
Installation & Safety
Installation Guidelines
- Install on a solid, level concrete foundation to reduce vibration
- Ensure proper airflow around the generator for adequate cooling
- Direct exhaust fumes safely away from buildings and working areas
- Have all electrical wiring carried out by qualified electricians
- Use clean diesel fuel and install fuel lines securely to prevent leaks
- Ensure proper earthing to protect against electrical hazards
- Maintain sufficient clearance space around the generator for servicing
Safety Guidelines
- Only trained personnel should operate or service the generator
- Keep flammable materials away and maintain fire extinguishers nearby
- Use hearing protection in high-noise environments
- Avoid contact with engine and exhaust components during or after operation
- Regularly inspect fuel lines, electrical connections, and cooling systems
- Always follow correct shutdown procedures before performing maintenance
Installation and operation should always follow local safety regulations. Ensure proper earthing, qualified electrical connections, and keep fire suppression equipment accessible at all times.